Send message
Ask a question
Pricing/Quote
List of suppliers/where can I buy
Sample request
I have read and agree to the terms and conditions of usage and The Building Centre's Privacy Policy. Your request will be sent and shared to the selected manufacturers you submit a request to.

Find products

Use our product finder to search for products and materials

Subscribe to our newsletter to receive news about events and exhibitions, innovation and materials on the latest building product innovations, case studies and more.
I have read and agree to the terms and conditions of usage and The Building Centre's Privacy Policy.
Back to search

SATK30 Indirect Heat Interface Unit

Altecnic Ltd

The SATK30 is the complete solution for instantaneous hot water
production and space heating control.

The twin plate design hydraulically separates both domestic and space heating from the central primary supply.

The internal electronic control unit ensures maximum efficiency and
control but also incorporates other additional important features.
The standard unit can be set to hold a stable heating flow
temperature, to suit the installation (radiators, UFH for example), but
crucially, can also be set to vary the heating flow temperature
automatically depending on the temperature of the heating return
water.

This allows the unit to automatically compensate for changes due to
external influences, such as outside temperature etc. thereby ensuring that the unit and the system operate at maximum efficiency
The unit also features a pump bypass to protect the pump, in case of
complete radiator TRV shutdown.

The SATK30 is extremely compact in design and lightweight,
benefitting both installers and architects.

The unit has a fully insulated front cover, manufactured from
expanded PPE, which includes a sliding window to allow the tenant to
access the integral heat meter (if installed).

The unit can be fitted with an optional isolation module which allows
the domestic hot water (DHW) and heating circuits to be remotely
isolated by the building owner/landlord etc. via a computer with
internet access.

Product categories


Specifications

Material(s)
Front Cover- PPE
General performance
Minimum Differential Pressure- 0.35 bar
Material(s)
Expansion Vessel- Steel
General performance
Maximum Temperature- 85C
Material(s)
Connecting Pipework- Stainless Steel
General performance
Medium- Water
Material(s)
Pump- UPS2 15/60
Optional features
Heating Set Point- 25 to 75C
Material(s)
Electronic Controller- 230 V -50Hz
Optional features
DHW Temperature- 42 to 60C
General performance
Maximum Static Working Pressure- 16 bar- primary
Material(s)
Frame- Painted Steel
General performance
Primary Differential Pressure Capability- 1.65 bar